Skip to main content

FF756N

16521 UV/IR² Flame Detector in Eexd - IIC T6 Flame Proof Housing
  • Highest immunity to false sources like arc welding, lightning, and solar blind
  • Tolerant of fumes, vapours, dust and mist
  • Unaffected by convection currents, draughts or wind
  • Suitable for indoor and outdoor areas
  • Proven response to multiple fuel types due to multi-spectrum detection
View all

At a glance

General

The FF756N is a UV / IR² flame detector in a flame proof housing. UV / IR² models have excellent response to flame while providing immunity to extraneous sources. New micro-processor technology makes the detectors independent of flame intensity enabling it to operate through smoke, a layer of oil, dust, or water vapor. A high and low sensitivity setting according to EN54-10 is provided.
Successor of FF756

Operation

The FF756N has a UV sensor and two IR sensors which respond to different wavelengths of both the ultra-violet and the infrared spectrum. The signals from these sensors are processed by the detector and checked for characteristics of a flame. The simultaneous detection of both the UV and the IR light by the sensors will signal an alarm. False alarms from flickering sunlight, arc welding and lightning are eliminated by a combination of UV and dual IR signal processing techniques.
The FF756N has selectable output options of relay contacts or 4-20mA signal, as standard.

Installer and maintenance friendly

The units can be wired as conventional 2 wire, 4-20 mA, or relay contacts (fire, fault and pre alarm) in latching or non-latching operation. Remote test inputs are available to activate self-test.

A stainless steel adjustable bracket and weather shield is also available.

The units are tolerant to vibration, and wind does not affect the performance. The IR² unit has excellent tolerance to detector window contamination and can detect flame through glass windows.

A flame sensor test unit is available for accurate testing of the detectors.

Details

  • Highest immunity to false sources like arc welding, lightning, and solar blind
  • Tolerant of fumes, vapours, dust and mist
  • Unaffected by convection currents, draughts or wind
  • Suitable for indoor and outdoor areas
  • Proven response to multiple fuel types due to multi-spectrum detection
  • Proven response to multiple fuel types
  • Selectable output options,response speed and sensitivity levels
  • Built in auto and manual test
  • Low current consumption

Technical specifications

Electrical
Operating voltage
14 to 30 VDC
Current consumption
8 mA (Quiescent - RL2 energised)
4 mA (Quiescent - current loop, RL2 off)
3 mA (Quiescent - RL2 off)
28 mA (Alarm - RL1 & RL2 energised)
20 mA (Alarm - current loop, RL1 & 2 off)
28 mA (Alarm - RL1 energised)
Cable specification
1.0 to 4.0 mm²
Detection
Field of view
< 90° Cone
Range
< 50 m
Lateral detection
< 45°
Optical wave length (all languages) 185 to 260 nm (UV)
0.75 to 2.7 μm (IR)
Response time (all languages) 8 s @ 25 m (n-Heptane - yellow flame of 0.3 x 0.3 m @ 25 m)
12 s @ 25 m (Methylated Spirit - clear flame of 0.5 x 0.5 m @ 25 m)
16 s @ 25 m (Hydrogen - non-visible flame of 0.1 x 0.5 m @ 12 m)
Output
Output quantity
2
Output type and rating
Normally open or Normally closed (< 1 A @ 50 VDC - < 30 W resistive load)
Programmable
Latching or non-latching
Physical
Physical dimensions
150 x 146 x 137 mm (h x w x d)
Net weight
2.5 kg
Colour
Red
Mounting type
Surface mount
Cable entries
3 x 20 mm
Material (body)
Copper free aluminium alloy
Fixing centres
58 mm
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Storage temperature
-20 to +65°C
Relative humidity
< 95% noncondensing
Environment
Exd
Indoor
Outdoor
IP rating
IP66
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CENELEC/ATEX
CPR
Voluntary marks
LPCB
VdS
Standards
EN54-10
IEC marking
EEx d IIC T6