FF756N
16521 UV/IR² Flame Detector in Eexd - IIC T6 Flame Proof Housing
- Highest immunity to false sources like arc welding, lightning, and solar blind
- Tolerant of fumes, vapours, dust and mist
- Unaffected by convection currents, draughts or wind
- Suitable for indoor and outdoor areas
- Proven response to multiple fuel types due to multi-spectrum detection
At a glance
General
The FF756N is a UV / IR² flame detector in a flame proof housing. UV / IR² models have excellent response to flame while providing immunity to extraneous sources. New micro-processor technology makes the detectors independent of flame intensity enabling it to operate through smoke, a layer of oil, dust, or water vapor. A high and low sensitivity setting according to EN54-10 is provided.
Successor of FF756
Operation
The FF756N has a UV sensor and two IR sensors which respond to different wavelengths of both the ultra-violet and the infrared spectrum. The signals from these sensors are processed by the detector and checked for characteristics of a flame. The simultaneous detection of both the UV and the IR light by the sensors will signal an alarm. False alarms from flickering sunlight, arc welding and lightning are eliminated by a combination of UV and dual IR signal processing techniques.
The FF756N has selectable output options of relay contacts or 4-20mA signal, as standard.
Installer and maintenance friendly
The units can be wired as conventional 2 wire, 4-20 mA, or relay contacts (fire, fault and pre alarm) in latching or non-latching operation. Remote test inputs are available to activate self-test.
A stainless steel adjustable bracket and weather shield is also available.
The units are tolerant to vibration, and wind does not affect the performance. The IR² unit has excellent tolerance to detector window contamination and can detect flame through glass windows.
A flame sensor test unit is available for accurate testing of the detectors.
A stainless steel adjustable bracket and weather shield is also available.
The units are tolerant to vibration, and wind does not affect the performance. The IR² unit has excellent tolerance to detector window contamination and can detect flame through glass windows.
A flame sensor test unit is available for accurate testing of the detectors.
Details
- Highest immunity to false sources like arc welding, lightning, and solar blind
- Tolerant of fumes, vapours, dust and mist
- Unaffected by convection currents, draughts or wind
- Suitable for indoor and outdoor areas
- Proven response to multiple fuel types due to multi-spectrum detection
- Proven response to multiple fuel types
- Selectable output options,response speed and sensitivity levels
- Built in auto and manual test
- Low current consumption
Technical specifications
| Electrical | ||
|---|---|---|
| Operating voltage |
14 to 30 VDC
|
|
| Current consumption |
8 mA (Quiescent - RL2 energised)
4 mA (Quiescent - current loop, RL2 off)
3 mA (Quiescent - RL2 off)
28 mA (Alarm - RL1 & RL2 energised)
20 mA (Alarm - current loop, RL1 & 2 off)
28 mA (Alarm - RL1 energised)
|
|
| Cable specification |
1.0 to 4.0 mm²
|
|
| Detection | ||
|---|---|---|
| Field of view |
< 90° Cone
|
|
| Range |
< 50 m
|
|
| Lateral detection |
< 45°
|
|
| Optical wave length (all languages) | 185 to 260 nm (UV) | |
| 0.75 to 2.7 μm (IR) | ||
| Response time (all languages) | 8 s @ 25 m (n-Heptane - yellow flame of 0.3 x 0.3 m @ 25 m) | |
| 12 s @ 25 m (Methylated Spirit - clear flame of 0.5 x 0.5 m @ 25 m) | ||
| 16 s @ 25 m (Hydrogen - non-visible flame of 0.1 x 0.5 m @ 12 m) | ||
| Output | ||
|---|---|---|
| Output quantity |
2
|
|
| Output type and rating |
Normally open or Normally closed (< 1 A @ 50 VDC - < 30 W resistive load)
|
|
| Programmable |
Latching or non-latching
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
150 x 146 x 137 mm (h x w x d)
|
|
| Net weight |
2.5 kg
|
|
| Colour |
Red
|
|
| Mounting type |
Surface mount
|
|
| Cable entries |
3 x 20 mm
|
|
| Material (body) |
Copper free aluminium alloy
|
|
| Fixing centres |
58 mm
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +55°C
|
|
| Storage temperature |
-20 to +65°C
|
|
| Relative humidity |
< 95% noncondensing
|
|
| Environment |
Exd
Indoor
Outdoor
|
|
| IP rating |
IP66
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
| Certification |
CENELEC/ATEX
CPR
|
|
| Voluntary marks |
LPCB
VdS
|
|
| Standards |
EN54-10
|
|
| IEC marking | ||
|---|---|---|
| EEx d IIC T6 | ||
Downloads
All downloadsDatasheet
Other EU certificate
Other EU certificate
ATEX/IEC Certificate
Other EU certificate
Approval of Components and Systems
Other EU certificate
IECEx Certificate of Conformity
Other EU certificate
Supplementary EU - Type Examination Certificate
Other EU certificate
EU - Type Examination Certificate
Other EU certificate
Type Examination Certificate
Other EU certificate
Approval of Components and Systems
Product range overview
CPD / CPR
Certificates
Non EU certificate
LPC - Certificate of Product Approval
Non EU certificate
BRE Global Ltd./LPCB - Certificate of UKCA approval constancy of performance
DoP
.Others - Declaration of Performance
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.